Introduction

This test furnace simulates the actual temperature rise process during a  fire, meeting the requirements for conducting fire resistance limit tests on  specimens to comprehensively evaluate the weathering performance of structural  components.


建筑构件耐火燃烧水平炉.png

Standards

(1)ISO 834-1:2025 Fire-resistance tests — Elements of building construction  Part 1: General requirements

(2)GB/T 9978.1-2008 —Fire Resistance Test Methods for Building  Components—Part 1: General Requirements

(3)GB/T 9978.3-2008 — Fire Resistance Test Methods for Building  Components—Part 3: Notes on Test Methods and Application of Test Data

(4)GB/T 9978.5-2008—Fire Resistance Test Methods for Building Components -  Part 5: Special Requirements for Load-bearing Horizontal Partition  Components

(5)GB/T 9978.6-2008—Fire Resistance Test Methods for Building Components -  Part 6: Special Requirements for Beams

(6)GB/T 9978.7-2008—Fire Resistance Test Methods for Building Components -  Part 7: Special Requirements for Columns

(7)EN 1363-1 Fire resistance tests - Part 1: General Requirements

(8)EN 1363-2 Fire resistance tests - Part 2: Alternative and additional  procedures

(9)EN 1364-1 Fire resistance tests for non-loadbearing elements - Part 1:  Walls

(10)EN 1364-2 Fire resistance tests for non-loadbearing elements - Part 2:  Ceilings

(11)EN 1365-1 Fire resistance tests for loadbearing elements Part 1 :  Walls

(12)EN 1365-2 Fire resistance tests forloadbearing elements Part 2: Floors  and roofs

(12)EN 1634-1 Fire resistance tests for door and shutter assemblies

Technical Parameters

Parameter

Specification

Furnace Type

Horizontal refractory furnace

Chamber Size

4.0m × 4.0m × 2m

Fuel

Natural gas

Maximum Operating Temperature

1300℃

Number of Burners

10 sets

Total Gas Consumption

≤300m³/h

Exhaust Gas Temperature

≤280℃

Exhaust Air Volume

≈20000m³/h

Furnace Wall Temperature

≤45℃

Insulation Material

Built-in chromium-containing cotton modules

Thermocouples

12 in-furnace thermocouples, 48 warm-zone thermocouples, 1  movable thermocouple, 1 ambient thermocoupleThermocouples comply with GB/T  16839.1: Type K (nickel-chromium/nickel-silicon) with φ2mm diameter, fitted with  heat-resistant steel outer sleeves and ceramic inner sleeves. Protrusion length  from sleeve ≥25mm- In-furnace range: 0℃~1300℃, accuracy: ±15℃- Backside surface  range: 0℃~800℃, accuracy: ±4℃- Movable range: 0℃~900℃, accuracy: ±4℃- Ambient  range: -10℃~100℃, accuracy: ±1℃

Observation Windows

2 on the rear wall of the furnace body

Combustion Control Mode

Proportional combustion, automatic pressure control, automatic  temperature adjustment, temperature curve program control, computer-assisted  management

Exhaust Mode

Rear-wall mechanical exhaust

Computer Configuration

Tsinghua Tongfang

Equipment Structure and Description

The complete set of equipment includes a furnace body conforming to GB/T  9978.1-2008, a test frame, a smoke exhaust and air supply system, a test control  system (including data acquisition system, thermocouples, furnace pressure  control system, deformation measurement system, and video recording and  photography system), an integrity measuring instrument, a combustion and gas  supply system, and a servo hydraulic loading system. It features calibration  functions to ensure that the temperature and pressure values and distribution  meet the standard requirements.

Furnace Structure

The internal dimensions of the furnace are 4200mm (D) × 3000mm (W) × 2000mm  (H). The total height of the furnace including the fume hood is 5.3m. The main  body of the test furnace adopts a steel structure

frame. The furnace lining material uses high-temperature resistant insulation  material with a density of less than 1000 kg/m³. The thickness of the furnace  lining material is not less than 300mm.

Steel Structure & Material Parameters

Serial No.

Steel Structure

Material Parameter

1

Furnace Body Steel Plate

Material: Q235, wall thickness: 4mm

2

Furnace Body Column

Material: Q235, channel steel

3

Furnace Body Frame

Material: Q235, channel steel / I-beam / rectangular  tube

4

Furnace Wall Reinforcement Bar

Material: Q235, channel steel

Furnace Body Refractory Materials

The furnace body uses refractory fiber insulation, with a minimum thickness  of 300mm. The maximum operating temperature is 1430℃, and the long-term working  temperature is no less than 1400℃. The linear shrinkage after firing at 1400℃ is  less than 0.5%, and the thermal conductivity is better than 0.4 W/m·K.  Industrial refractory adhesive is used for bonding, with a service temperature  of no less than 1400℃.

Parameter

Specification

Chemical Composition

Al₂O₃ ≥ 35%, average: 35.1; SiO₂ ≥ 55%, average: 49.7; ZrO₂ ≥  13%, average: 15

Operating Temperature

1400℃

Bulk Density (kg/m³)

≥ 210, average: 210

Linear Change Rate (%)

≤ 0.5%

Thermal Conductivity (W/m·K)

- At average temperature 600℃: ≤ 0.14 (0.16), typical: 0.12  (0.14)- At average temperature 800℃: ≤ 0.22 (0.25), typical: 0.17 (0.20)- At  average temperature 1000℃: ≤ 0.32 (0.37), typical: 0.24  (0.28)


Note:QINSUN is very in place for textile testing and quality control,we have our own textile testing lab. Our textile testing equipment and testing methods are in the leading position in the industry. We have passed the textile testing certification and iso textile testing standards issued by a number of testing,We can provide textile testing equipment pdf manual. Sufficient inventory, big discounts, limited time promotion, Order now!

Leave Message Get Price